Condensing Units

Brand

Model No

U-4 to U-6LA1E5

Details

Cooling Capacity - 11.2 to 15.5KW
Heating Capacity - 12.5 to 16.0KW
  • Refrigerant charge free system (no additional refrigerant required).
  • Very quiet outdoor units.
  • Flexible installation and easy set up.
  • Easy fault finding function.
  • Space saving design.

Detailed Specifications

  • Specifications
  • MODEL U-4LA1E5
  • Compressor Type Inverter Scroll
  • Power Source 1 Phase 220-240V / 50Hz
  • Nominal Cooling Capacity kW 11.2
  • Nominal Heating Capacity kW 12.5
  • Efficiency (EER / COP) kW 3.61 / 4.11
  • Running Current Nominal Amp 13.60
  • Dimensions (H x W x D) mm 1340 x 900 x 350
  • Weight kg 115
  • Refrigerant Charge (R410A) kg 7.0
  • Sound Pressure Level dB(A) 54
  • Indoor Unit Combination Wall Mtd S-22 to S-90
  • Cassette S-22 to S-90
  • Ducted S-22 to S-90
  • Min / Max No of Connected Indoor Units 2 / 6 units
  • Max Total Pipe Run m 90
  • Operating Range Cooling (degC) -5 to 46, Heating -15 to 24
  • Specifications
  • MODEL U-5LA1E5
  • Compressor Type Inverter Scroll
  • Power Source 1 Phase 220-240V / 50Hz
  • Nominal Cooling Capacity kW 14.0
  • Nominal Heating Capacity kW 16.0
  • Efficiency (EER / COP) kW 3.25 / 4.03
  • Running Current Nominal Amp 19.00
  • Dimensions (H x W x D) mm 1340 x 900 x 350
  • Weight kg 123
  • Refrigerant Charge (R410A) kg 8.0
  • Sound Pressure Level dB(A) 55
  • Indoor Unit Combination Wall Mtd S-22 to S-90
  • Cassette S-22 to S-90
  • Ducted S-22 to S-90
  • Min / Max No of Connected Indoor Units 2 / 8 units
  • Max Total Pipe Run m 90
  • Operating Range Cooling (degC) -5 to 46, Heating -15 to 24
  • Specifications
  • MODEL U-6LA1E5
  • Compressor Type Inverter Scroll
  • Power Source 1 Phase 220-240V / 50Hz
  • Nominal Cooling Capacity kW 15.5
  • Nominal Heating Capacity kW 18.00
  • Efficiency (EER / COP) kW 3.01/ 3.84
  • Running Current Nominal Amp 22.50
  • Dimensions (H x W x D) mm 1340 x 900 x 350
  • Weight kg 123
  • Refrigerant Charge (R410A) kg 8
  • Sound Pressure Level dB(A) 57
  • Indoor Unit Combination Wall Mtd S-22 to S-90
  • Cassette S-22 to S-90
  • Ducted S-22 to S-90
  • Min / Max No of Connected Indoor Units 2 / 8 units
  • Max Total Pipe Run m 90
  • Operating Range Cooling (degC) -5 to 46, Heating -15 to 24
print